# Global Settings: Alerts Management

Which alerts fire, at what threshold and severity, after how long, and who is notified — the highest-leverage page in Settings.

## What this page is for

Alerts Management is where you decide what the platform tells you about. Every alert you have ever received traces back to a rule configured here: which condition is watched, how bad it has to be, how long it has to persist, how serious it is called, and who hears about it.

It is the highest-leverage page in Settings, and the one most worth revisiting. Too loose and real faults sit unnoticed inside the noise; too tight and the team stops reading alerts at all.

![The Alerts Management page on the General tab: the searchable list of alert codes on the left and the selected alert’s escalation rules on the right.](https://cdn-assets.productfruits.com/ed224d53-6de8-4964-a43b-19607af725f4)

## Layout

Three tabs across the top group the alert catalogue by domain:

-   **General** — generation, communication, inverters, strings, meters, sensors, trackers, grid quality, EV chargers and invoicing. Around thirty codes.
-   **Performance** — performance ratio, adjusted PR, PR-temperature, availability, their relative equivalents, and tracker angle deviation.
-   **Storage** — the battery catalogue, by far the largest: BMS and PCS faults, cell voltage and temperature, insulation, fire and emergency stop, plus vendor-specific codes for Contel, Sungrow, Kstar, Jinko and Tesla.

Within each tab, the left column lists the alert codes with a **Search alert codes…** box above them. Selecting one opens its configuration on the right, headed by the human-readable name and the machine code underneath — for example *Inverter Performance* and `INVERTER_LOW_PERFORMANCE`. Quote that machine code when raising a support question; it is unambiguous.

## Escalation Rules

Each alert has a **Default Rule** and can have additional rules beneath it. This is what makes escalation possible: the same condition can be minor for four hours and serious after twelve, notifying different people at each stage.

Each rule has an **Active** toggle, and every rule except the default can be renamed and deleted.

| Field | What it does |
| --- | --- |
| Display Description | The text shown on the alert itself. Use it to say what to do, not just what happened. |
| Threshold | A comparison (Below, Above) and a percentage. The point at which the condition counts as breached. |
| Severity | How serious the alert is called, for example High. Drives sorting and prioritisation in the alert lists. |
| Alert After (Hours) | How long the condition must persist before the alert is raised. 0 means immediately. |
| SLA and SLA Units | The response time expected once the alert is open, in hours or days. Used to flag overdue alerts. |
| Notification Recipients | Who is notified. Leave empty and the alert still appears in the portal but nobody is emailed. |

There is also an **Internal** checkbox at the top right of the alert. Internal alerts are kept for enSights use and are not surfaced to customers.

![The Performance tab of Alerts Management, showing performance-ratio and availability alert codes and the Relative PR rule with its threshold, severity, delay, SLA and recipients.](https://cdn-assets.productfruits.com/8345c695-49e5-46df-9271-978045c82dcb)

### How to add an escalation step

1.  Select the alert code in the left list.
2.  Press **Add Rule**.
3.  Name the rule, then set its threshold, severity, delay, SLA and recipients.
4.  Check the **Active** toggle is on.
5.  Press **Update** at the bottom of the page.

A common shape: the default rule fires at a mild threshold with a long delay and notifies the monitoring team; a second rule fires at a worse threshold with a shorter delay and notifies the account manager as well.

## Excluded Systems

At the bottom of each alert is a collapsible **Excluded Systems** section with a count, listing sites for which this alert has been suppressed. Each row has a **Restore** link, and **Restore All** clears the list.

Exclusions are how a known, accepted condition at one site stops generating alerts without weakening the rule for everyone else — a site awaiting a part, or one whose sensor is known bad. Review the list periodically: an exclusion added during an incident and never removed is a fault you have permanently agreed not to see.

## How to tune a noisy alert

1.  Find the code in the left list — search by name or by machine code.
2.  Look at **Alert After (Hours)** first. Raising it filters transient conditions without hiding real ones, and is usually a better first move than moving the threshold.
3.  If the alert is genuinely mis-scoped, adjust the **Threshold**.
4.  If only a handful of sites are responsible, exclude those sites rather than changing the rule.
5.  Press **Update**, then watch the next day or two before changing anything else.

![The Storage tab of Alerts Management, showing the battery alert catalogue and the selected alert marked Internal, with its Excluded Systems section below.](https://cdn-assets.productfruits.com/2468babb-b516-4c0d-b2e2-1fcd592e1c12)

## Notes

-   Changes are account-wide and apply from the next evaluation. Alerts already open are not re-evaluated.
-   Turning a rule *inactive* is reversible and leaves the configuration intact — prefer it to deleting a rule you may want back.
-   An alert with no recipients still appears in the portal. Silence is not the same as absence.
-   Change one rule at a time. Loosening several thresholds at once makes it impossible to tell which change caused the flood.
-   Vendor-specific storage codes only fire on hardware from that vendor — the Contel, Sungrow, Kstar, Jinko and Tesla families are irrelevant if you run none of them.