# System Settings: Alerts Management

Which conditions raise an alert on a site, at what threshold and severity, after how long, and who hears about it.

*Fleet Management → a system's ⋮ menu → Edit → Alerts Management*

## How alerting works

Every insight you see on the Insights & Alerts page came from a rule on this tab. A rule pairs a **condition** with a **threshold**, a **severity**, a **delay** and a list of **recipients**. Tuning alerts is almost always about the delay and the threshold, not about switching rules off.

The tab has three sub-tabs: **General**, **Performance** and **Indicators**.

![The Alerts Management tab with the alert-code list and escalation rules](https://cdn-assets.productfruits.com/94f3aab9-0c9b-4475-a896-99b1aa275ae5)

## The fields on a rule

-   **Internal** — keep the alert inside your team. Internal alerts do not reach customer-facing recipients and are hidden from the insights list unless *Show Internal Alerts* is on in its filter.
-   **Display Description** — the wording that appears on the insight. Worth customising for rules your customers see.
-   **Threshold** — the value, with *Above* or *Below* and its unit (usually %).
-   **Severity** — High, Medium or Low. This becomes the Priority column and drives who gets woken up.
-   **Alert After (Hours)** — how long the condition must hold before the alert opens. The single most useful field for reducing noise.
-   **SLA** and **SLA Units** — the response commitment for this alert. The insights list can then filter on *Exceeded from SLA*.
-   **Notification Recipients** — who is notified.
-   **Add Rule** — add another rule for the same condition, for example a Medium alert at −5% and a High alert at −15%.

## General — availability and equipment faults

These rules answer "is the equipment alive and healthy". They cover:

-   **System level** — no energy yield from system, communication error in system.
-   **Inverters** — no yield, communication error, late awakening, low performance, high temperature, DC voltage too high.
-   **Strings** — no current, no voltage, no data.
-   **Electrical faults** — isolation fault (the array is not properly isolated from ground), phase unbalance, grid voltage too high or low, AC frequency too high or low, power factor below threshold.
-   **Meters** — no generation, no communication.
-   **Sensors and trackers** — sensor not communicating, tracker unit not communicating.
-   **Site equipment** — cleaning robot errors (wash error, power error, water amount), EV charger faults and failed transactions, PPC setpoint below threshold.
-   **Vendor pass-through** — alerts raised by the manufacturer's own platform, such as SolarEdge alerts.
-   **Process** — missing draft invoice, indicator operational status.

Availability rules rarely need thresholds — they need sensible delays. A communication rule with a one-hour delay is normal; fifteen minutes will fire on every network blip.

## Performance — output below expectation

These rules compare the site against a reference and fire when it falls short. Two families:

-   **Relative** rules compare the site against its peers or its own history: relative PR, relative APR, relative PR-temperature, relative availability, and tracker angle deviation.
-   **Absolute** rules compare against a fixed threshold and can fire in both directions: PR, adjusted PR (APR), PR-temperature and availability each have an *above* and a *below* variant.

The *above* variants are not a mistake — a PR that is impossibly high is usually a data or configuration fault worth catching.

Performance rules depend on the site's plan: without the P-50 monthly plan in the Performance tab, there is no expectation to deviate from.

## Indicators

Alerts on custom data points the site reports, listed as **Source Name**, **Display Name** and **Type (Alert On)**. This is how a site-specific signal — a door contact, a pump status, a bespoke SCADA register — becomes a monitored condition. If the table says "No indicators configured", none have been mapped for this site.

## Common tasks

**Reduce alert noise without going blind.** Raise *Alert After (Hours)* on the communication rules and keep the thresholds. You still learn about real outages, just not about every blip.

**Escalate only the serious cases.** Add two rules for the same condition: Low severity at a small deviation with no external recipients, High severity at a large deviation with the on-call list.

**Give an off-taker their own wording.** Set *Display Description* on the rules they see and leave the technical rules Internal.

**Hold a site quiet during works.** Use *Suspend Alerts* on the Advanced tab rather than editing every rule.

## Common questions

**Do these settings apply to every site?**  
No — Alerts Management is per system. Configure a representative site, then replicate the pattern; for fleet-wide conventions talk to your enSights contact about templates.

**An alert never fires even though the condition is obviously true.**  
Check the alerting window on the Advanced tab (*Start/Stop Alerting At*) and the validation window. A condition that only occurs outside the window will not alert.

**Who receives notifications if I leave recipients empty?**  
The alert still opens as an insight in the portal; nobody is notified outside it.