Global Settings: Performance
What this page is for
Performance defines the numeric boundaries the platform uses to judge assets. It does not measure anything β it decides where "fine" ends and "a problem" begins, and which colour a figure is painted. Every dashboard, list and status indicator that shows performance reads its bands from here.
Systems Performance
Three bands describing how far a system's actual energy may deviate from its expected energy before it is classed as underperforming. Expected energy is the weather-adjusted expectation, so these bands are about the gap between what the weather allowed and what the site produced.
Band | Rule | Default |
|---|---|---|
Optimal | Deviation within | 5% or less |
Average | Deviation between | 5% and 10% |
Low | Deviation beyond | 10% or more |
The bands are continuous: the Optimal ceiling is the Average floor, and the Average ceiling is the Low floor. Editing the Average pair therefore moves the other two boundaries with it β you set two numbers, not six. Each band also carries a colour swatch, which is what you see in system lists.
Reset to Default, at the top right of the panel, restores the shipped 5% / 10% values.
Choosing the numbers
Tight bands surface small losses early but flag ordinary measurement noise; wide bands are quiet but let real losses accumulate. A useful approach is to start at the defaults, look at how many systems land in Low over a normal week, and adjust until that population is small enough to act on but not so small that genuine losses hide inside Average.
RTE Settings
A single Threshold percentage for round-trip efficiency on battery systems β the share of energy put into a battery that comes back out again. Below this figure, the battery is treated as underperforming.
Round-trip efficiency falls naturally with age and with operating temperature, so this threshold is effectively the line at which degradation stops being expected and starts being worth investigating.
SOH Settings
A single Threshold percentage for State of Health β the battery's present usable capacity as a share of its original rated capacity. Below this figure, the battery is flagged.
Warranties and offtake agreements often specify a State of Health floor. Setting the threshold to match that figure turns a contractual obligation into something the platform watches for you.
Energy Accumulation
Some devices measure both directions: what the site exports and what it imports from the grid. Imports arrive as negative readings. Energy Accumulation decides how those negative readings are counted when enSights adds interval readings up into daily and monthly totals.
Meter-reported PV sites only. Energy Accumulation applies to PV sites whose production is reported by a meter that measures both directions, such as eGauge. Sites reported by inverters, such as SolarEdge, are not affected, and their system settings do not show the Energy Accumulation card.
Option | What it does | Total |
|---|---|---|
Ignore negative values (default) | Negative readings are dropped. Only positive production is counted. Same as before this setting existed. | Export only |
Respect negative values as absolute value | Every reading counts by its size: a β5 kWh reading adds 5 kWh. Use it for gross throughput. | Export + import. Never below zero. |
Respect negative values as net-sum value | Negative readings are subtracted from production, so the total matches the source meter. | Export β import. Can go below zero for a day or a month. |
Hover the β next to each option for the same explanation in the product.
- Account default and system override. The value here is the account default. A system can set its own value in System Settings β Advanced, and the system value wins. Systems with their own setting are listed under Excluded Systems, where Restore (or Restore All) returns them to the default.
- What changes when you update it. You confirm the change first. Saved readings never change; only how they are added up. Systems that follow the default are recalculated: daily and monthly totals, charts and summaries.
- Production-only devices have no negative readings, so every option gives the same result for them.
- Who can change it: users with the Edit PV permission. Everyone else sees it read-only.
Which one to pick. Choose net-sum when your totals must reconcile with a net meter such as eGauge. Choose absolute value when you want gross energy through the meter. Leave Ignore when the site only produces.
Azimuth Convention
Panel azimuth, the compass direction the panels face, is written with two different numbering systems. The same south-facing array is 0Β° in one and 180Β° in the other. This setting tells enSights which one your azimuth values use.
Convention | How the numbers read |
|---|---|
South-referenced (PVsyst) | 0Β° = South Β· β90Β° = East Β· +90Β° = West Β· Β±180Β° = North |
Compass / True North (NREL, PVWatts) | 0Β° = North Β· 90Β° = East Β· 180Β° = South Β· 270Β° = West |
The Account default applies to every system that has no setting of its own. To use the other convention on one system, open the system's Edit β Advanced β Calculations β Azimuth Convention. A system's own setting wins over the account default. A system shared with you from another account follows its owner's setting and can only be changed there.
Why it matters. If the convention is wrong, enSights models the panels facing the wrong way, and POA irradiance and weather-adjusted expected energy can be off by 50% or more. If a site's POA is far above or below its on-site sensor, check this setting first. Switching convention never changes the azimuth numbers you saved, only how they are read, and the expected figures are recalculated afterwards. To convert by hand: Compass = PVsyst + 180Β°.
Performance Colors
Three percentage ranges that drive the colour coding used across dashboards:
Band | Default range |
|---|---|
Above Average | 80% to 120% |
Average | 70% to 80% |
Below Average | 0% to 70% |
Each band has its own colour swatch. Note that this is a separate scheme from Systems Performance: Systems Performance is about deviation from expectation, while Performance Colors bands an absolute performance percentage. Keep the two consistent in spirit, or the same site can read green on one screen and amber on another.
How to change a threshold
- Go to Settings β Global Settings β Performance.
- Type the new value into the field. Percentages only.
- Press Update at the bottom of the page.
Notes
- Changes apply account-wide and take effect on the next evaluation β they do not rewrite alerts that already fired.
- Bands must not overlap or leave gaps. If a value is rejected, check that it sits between its neighbours.
- These thresholds classify and colour. They are not the same as the alert thresholds in Alerts Management, which decide whether a notification is sent.
- Reset to Default affects the Systems Performance panel only.